General data
-
AC power (bi-directional): 3.3 kW
% p10/% -
Frequency: 50 or 60 Hz
%p20 /% -
THDi: <5%
-
Nominal DC voltage: 48 Vdc
% p31/% -
Controllable power factor (cap/ind): 0.5
-
Maximum altitude above sea level: 3000 m
-
Maximum operating temperature: 65°C (derating from 45°C)
-
Minimum operating temperature: -20°C
-
Maximum operating humidity: %p59 /% RH
-
Weight: 2 kg
Nominal AC voltage: 230 Vac
Peak efficiency (bi-directional): 96.5%
Charging mode / input
-
Voltage range (according to selected grid codes): 100 - 277 Vac, Full load from 207 Vac % p78/%
-
Frequency: 45 - 66 Hz
Charging mode / output
-
Voltage range (standard): 42.2 - 59.0 Vdc
- % p99/% Voltage range (extended) *1 : 42.0 - 65.0 Vdc
-
Dynamic control % p109/% - 90% / 90 - 10%: 5% in the range 50 ms
-
Max ripple %p119 /% mhz bw): 150 mV p-p
Inverter mode / input
- %p129 /%
-
Maximum current: 71 A
Voltage range (nominal range): 44-59 Vdc, Full load from 49 Vdc
Inverter Mode/Output
-
Voltage Range (according to set network codes): 100 - 277 Vac, Full load from 207 Vac
-
Maximum current: 16 A %p156 /%
Standards and specifications
-
Internal communication: CAN-bus %p166/ %
-
Safety: IEC/EN 62109-1, IEC/EN 62109-2, IEC/EN 62368-1, IEC/EN 60950-1
%p175/ % -
AC network: VDE-AR-N 4105, EN 50549-1, TR 3.3.1, AS/NZS 4777.2, EREC G99
%p184/ % -
EMC: IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4
%p193/ % -
AC input protection: Fuse (25 A), relays mechanical with basic insulation and anti-islanding protection
-
DC input protection: Fuse (2 x 50 A), overvoltage protection, short-circuit protection, starting current limitation hot plug-in type.
-
Dimensions: Width 145 mm, Height 42 mm, Depth 339 mm
Environment: ETSI EN 300 019:2-2 (Class 2.3), ETSI EN 300 019:2-3 (Class 3.2)
%p203/ %Noise level (@1M I 25℃): 60 dBA
*1 Extended DC voltage range (special version with power reduction).