merXu

Cancel
Bidirectional AC/DC Energy Conversion Module PixiiBox 48/3300

Bidirectional AC/DC Energy Conversion Module PixiiBox 48/3300

Manufacturer
Pixii
Request for quotes
This offer is not active anymore. Add an inquiry and get offers from multiple sellers.
Parameters
Manufacturer
Pixii
Description

General data

  • AC power (bi-directional): 3.3 kW

  • % p10/%

    Nominal AC voltage: 230 Vac

  • Frequency: 50 or 60 Hz

    %p20 /%
  • THDi: <5%

  • Nominal DC voltage: 48 Vdc

  • % p31/%

    Peak efficiency (bi-directional): 96.5%

  • Controllable power factor (cap/ind): 0.5

  • Maximum altitude above sea level: 3000 m

  • Maximum operating temperature: 65°C (derating from 45°C)

  • Minimum operating temperature: -20°C

  • Maximum operating humidity: %p59 /% RH

  • Weight: 2 kg

Charging mode / input

  • Voltage range (according to selected grid codes): 100 - 277 Vac, Full load from 207 Vac % p78/%

  • Frequency: 45 - 66 Hz

Charging mode / output

  • Voltage range (standard): 42.2 - 59.0 Vdc

  • % p99/% Voltage range (extended) *1 : 42.0 - 65.0 Vdc

  • Dynamic control % p109/% - 90% / 90 - 10%: 5% in the range 50 ms

  • Max ripple %p119 /% mhz bw): 150 mV p-p

Inverter mode / input

    %p129 /%

    Voltage range (nominal range): 44-59 Vdc, Full load from 49 Vdc

  • Maximum current: 71 A

Inverter Mode/Output

  • Voltage Range (according to set network codes): 100 - 277 Vac, Full load from 207 Vac

  • Maximum current: 16 A %p156 /%

Standards and specifications

  • Internal communication: CAN-bus %p166/ %

  • Safety: IEC/EN 62109-1, IEC/EN 62109-2, IEC/EN 62368-1, IEC/EN 60950-1

    %p175/ %
  • AC network: VDE-AR-N 4105, EN 50549-1, TR 3.3.1, AS/NZS 4777.2, EREC G99

    %p184/ %
  • EMC: IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4

  • %p193/ %

    Environment: ETSI EN 300 019:2-2 (Class 2.3), ETSI EN 300 019:2-3 (Class 3.2)

    %p203/ %

    Noise level (@1M I 25℃): 60 dBA

  • AC input protection: Fuse (25 A), relays mechanical with basic insulation and anti-islanding protection

  • DC input protection: Fuse (2 x 50 A), overvoltage protection, short-circuit protection, starting current limitation hot plug-in type.

  • Dimensions: Width 145 mm, Height 42 mm, Depth 339 mm

*1 Extended DC voltage range (special version with power reduction).

New to buying at merXu?

It’s easier than you think. We provide you with a step-by-step guide.

Negotiate with the seller

You can contact the seller to adjust your order, negotiate the price, or inquire about other offers from their portfolio before making a purchase. Choose and click on the offer you are interested in. Find the button "SEND INQUIRY" on the right side of the offer and you will be moved directly to a chat with the seller.